Niagara 4 components: slots, facets, links and the priority array

What a Niagara component really is: properties, actions and topics, facets, status flags, extensions, proxy points, and how writable points decide which input wins.

By Berk · 16 November 2026 · 4 min read

Everything in a Niagara station is a component: a temperature point, a PID loop, a folder, a BACnet device, even the services that run alarms and histories. Once you understand how a component is put together, the rest of Niagara becomes a lot more predictable.

Slots: properties, actions and topics

A component is made of slots, and there are three kinds.

Properties hold data, such as a setpoint, a delay time, a units setting or the current output value.

Actions are things the component can be told to do. Overriding a point, acknowledging an alarm and resetting a run-hours counter are all actions. You run them by right-clicking in Workbench or from a button on a graphic, and they can also be fired by a link from another component.

Topics are events the component announces, such as an alarm being raised. They don’t store anything; they just tell other components that something happened.

Slots are either frozen, built into the component’s type and always there, or dynamic, added by you, like a link or an extra property. The slot sheet view shows every slot on a component, which is handy when something isn’t behaving and the property sheet is hiding the detail.

The views you’ll live in

  • Wire sheet. The graphical logic view: components as blocks, with links between their slots.
  • Property sheet. The settings of a component as a list.
  • Manager views. Driver views for discovering and adding devices and points, the alarm and history managers, and so on.

Double-clicking a component opens its default view. Right-click and choose Views to see the alternatives.

Out, facets and status

Most control components have an out slot holding their main value. Alongside it sit two things that matter a lot.

Facets control how the value is presented: units, decimal places, true/false text, and enum labels. They change what people see, not the value itself. A space temperature showing “21.43” with no units usually just needs its facets set to °C with one decimal place.

Status travels with every value and tells you whether you can trust it. Common flags include ok, fault, down (comms lost to the device), stale (not updated recently), overridden, alarm and disabled. Graphics and logic can react to status. For example, show a value in grey if it’s stale, or stop a sequence if a key input is in fault.

Extensions

Components can carry extensions, which are child components that add behaviour:

  • proxy extensions on points that come from a driver, holding the protocol details such as the BACnet object or the Modbus register
  • alarm extensions, which raise alarms when the value goes out of limits or changes state (see setting up alarms)
  • history extensions, which log the value over time (see histories and trending)
  • totaliser and run-hours extensions, which count time or accumulate a value

Proxy points

A proxy point is a Niagara point that represents data in a field device, such as a BACnet analogue input or a Modbus register. It always lives under its driver (Drivers › network › device › points) and its proxy extension holds the addressing.

Once a value is in Niagara as a proxy point, it behaves like any other component: you can link it, trend it, alarm it and put it on a graphic. Niagara normalises the data, so the rest of the station doesn’t need to care which protocol it came from.

Writable points and the priority array

Writable points (NumericWritable, BooleanWritable, EnumWritable and StringWritable) have sixteen input slots, in1 to in16, plus a fallback value. The highest-priority input that isn’t null wins, with in1 the highest. If every input is null, the fallback is used.

That’s what makes overrides work cleanly:

  • the emergency actions write at level 1
  • the operator override action writes at level 8, optionally with a duration
  • normal control logic is usually linked into a lower-priority input, often in16, or a level your company standard defines
  • set changes the fallback

When a point “won’t do what the logic says”, the first thing to check is whether something is sitting at a higher priority, most often a forgotten operator override at level 8. BACnet writable objects work on the same idea, which makes integration feel familiar.

Links connect a slot on one component to a slot on another, usually an out to an in. Drag from one slot to the other on the wire sheet. Links can also go into actions, so a boolean changing to true can, say, trigger a reset.

Keep wire sheets tidy: group logic into folders by plant item, name components clearly, and avoid long links snaking across a huge sheet. The next engineer, who might be you in two years’ time, will thank you.

Palettes

New components come from palettes: kitControl for logic blocks and loops, the driver palettes, schedule, alarm, history and kitPx for graphics, plus any custom palettes your company keeps. See palettes, templates and bulk deployment.

Next: tagging and hierarchies, which is where Niagara 4 really differs from AX.