Commissioning a JACE in Niagara 4: the wizard, certificates and the bits people miss
Getting a station onto a JACE: platform credentials, the Commissioning Wizard, modules, licences, IP and time settings, certificates, and checks before you leave.
Commissioning a JACE means taking a station you’ve built, in the office or on your laptop, and putting it on the controller in a working, secure state. Niagara’s Commissioning Wizard does most of the heavy lifting, but there are a few things it can’t decide for you, and they’re the ones that cause problems months later.
Before you start
Have these ready:
- The JACE’s licence, matched to its host ID and covering the drivers and device or point counts the job needs.
- The station, tested as far as possible, and backed up.
- The site IP details: address, subnet mask, gateway, DNS and NTP server, agreed with the client’s IT team. See IP networking for BMS engineers.
- A compatible Workbench. It should be the same Niagara version as the JACE, or newer.
- A plan for credentials: strong platform and station passwords, recorded somewhere the client controls.
First connection to the platform
A new JACE comes with factory network settings and default platform credentials, which are printed on the packaging or in the manufacturer’s documents. Niagara 4 makes you change the default platform credentials when you first log in. Choose something strong and unique, not one password reused on every JACE you own.
Always open a platform TLS connection rather than the legacy unencrypted one. The first time, Workbench will ask you to accept the JACE’s certificate.
Stop the local copy
If you’ve been running the same station on your own PC, stop it there before commissioning. Otherwise two copies of the same station end up on the network, with the same name and the same BACnet identity. That causes very confusing results.
The Commissioning Wizard
Right-click the platform connection and run the Commissioning Wizard. Depending on what you tick, it will:
- install licences and certificates
- copy the station onto the JACE, and set it to start automatically and restart if it fails
- install the software modules the station needs. The wizard works out the dependencies, but check that nothing is missing or on an odd version
- set TCP/IP settings, so the JACE ends up on the site network
- set the date, time and time zone, ideally pointing at the site’s NTP server
- reboot at the end to apply it all
Read every page rather than clicking Next. The IP and time-zone pages are where the expensive mistakes happen. A JACE set to the wrong IP address can need a site visit just to get back in.
Certificates and TLS
Out of the box, each Niagara host uses a self-signed certificate. That’s why browsers show security warnings and Workbench asks you to approve the host. It’s encrypted, but nothing proves the JACE is the JACE you think it is.
On a properly finished job, use Niagara’s certificate management to:
- Create a certificate for each JACE and supervisor that matches its real name or IP address, and have it signed, either by the client’s certificate authority or by your company’s own root certificate for the site.
- Install that certificate on the host and assign it to the platform and the station web server.
- Install the root certificate in the browsers (or the domain policy) that will view the system, so the warnings disappear for the right reasons.
The client’s IT team will often have a view on this, so ask early.
After commissioning: checks before you leave
- The station is running and set to auto-start. Power-cycle the JACE and check it comes back by itself.
- The time is right, in the right time zone, and syncing from NTP.
- Every driver network and device is ok, with nothing down, faulted or disabled by accident.
- The web interface works over HTTPS from a normal user’s PC.
- Default and test accounts are removed, and the admin passwords are recorded securely.
- A fresh backup of the commissioned station has been taken and stored off the JACE.
- The supervisor connection works, if there is one. See the Web Supervisor and the Niagara network.
The system passphrase
Niagara 4 encrypts sensitive data, such as passwords stored in drivers, using a system passphrase on each host. When you copy or restore a station between hosts, you may be asked for it. Record it with the other credentials, because losing it can mean re-entering every stored password in the station.
For the wider security picture, see BMS cyber security basics and users, roles and categories.