Niagara 4 alarms: classes, recipients, extensions and avoiding nuisance alarms
Setting up Niagara 4 alarms: alarm classes and routing, console and email recipients, alarm extensions, delays and inhibits, and alarm text that helps.
Good alarms are the difference between a BMS that helps people and one they’ve learned to ignore. In Niagara 4, alarm handling has two halves:
- detecting the alarm, on the point, with an alarm extension
- routing it, through the alarm service, to the people and places that need it
Get both right and operators see a short list of things that genuinely need action.
How the pieces fit
- An alarm extension on a point watches its value and decides when it’s in alarm.
- The extension sends the alarm to an alarm class.
- The alarm class decides priority, whether acknowledgement is needed, and where the alarm goes.
- Recipients linked to the class deliver it: the alarm console, email, another station, and so on.
- Everything is logged in the alarm database.
All of this sits under Services › AlarmService. Open its wire sheet to see the classes and recipients, and the links between them.
Alarm classes
Classes group alarms by how they should be handled. A typical set might be:
- Critical. Plant failures, frost risk, server room temperature. Goes to the alarm console, email and the out-of-hours contact. Acknowledgement required.
- Maintenance. Filters dirty, run hours due, sensor faults. Goes to the console and maybe a daily email. Acknowledgement optional.
- Comms. Devices offline. Goes to the console and the service contractor.
For each class you set the priority of each transition (to alarm, to fault, back to normal) and whether each one needs acknowledging. Keep the number of classes small and well defined, and put them in your station template so every job uses the same ones.
Recipients
- Console recipient. Shows alarms in the alarm console, in Workbench and in the browser.
- Email recipient. Sends emails through the station’s email service, which needs an outgoing mail account set up. Use a proper service account agreed with IT.
- Station recipient. Sends alarms on to another station, usually from a JACE up to the supervisor. See the Web Supervisor and the Niagara network.
Recipients can be limited to certain days and times, which is handy for sending out-of-hours alarms to a different address.
Alarm extensions
Add them to points from the alarm palette. The ones you’ll use most are:
Out of range, for numeric values. Set a high limit, a low limit, a deadband so the alarm doesn’t chatter around the limit, and which limits are active.
Change of state, for booleans. Alarm when a point goes to a set state, such as a fault input going true or a fire alarm signal operating.
Status alarm, which alarms on the point’s status rather than its value, for example when it goes into fault or down.
Command failure, which compares a command with its feedback. The fan was told to start but the airflow switch never proved, so raise an alarm. This is one of the most useful alarms on any site.
Settings that stop nuisance alarms
Time delays. Make the condition last a while before it alarms (to offnormal) and before it clears (to normal). A space that’s a degree out of range for thirty seconds isn’t an alarm.
Inhibit. Link a signal so alarms are suppressed when they’re meaningless, such as supply temperature alarms when the AHU is off, or the period just after start-up while plant settles.
Sensible limits. Base limits on what actually matters for the plant, not on the setpoint plus or minus one degree.
Comms alarms by device, not by point. One “AHU 3 controller offline” alarm beats fifty “point down” alarms.
Alarm text that helps
Each extension has text fields for the alarm message and instructions. Use them, and use substitution so the text picks up the point’s display name automatically. “AHU 3 supply air temperature high: check heating valve and frost thermostat” is useful. “Alarm: NumericPoint7 offnormal” isn’t.
Test it end to end
During commissioning, trigger every alarm properly and check:
- it appears in the console with the right class and text
- the email or other notification actually arrives
- acknowledgement works, and the alarm clears when the condition clears
- it reaches the supervisor, where there is one
An alarm that’s never been tested should be treated as an alarm that doesn’t work.