The Niagara 4 Web Supervisor: connecting JACEs, histories, alarms and master schedules

How a Niagara 4 supervisor works with its JACEs: adding stations securely, proxy points and virtuals, archiving histories, routing alarms and sharing schedules.

By Berk · 16 November 2026 · 4 min read

Once a site has more than one JACE, or the client wants a single front end across several buildings, you need a supervisor: a station hosted on a PC or server that pulls everything together. The supervisor and the JACEs talk to each other over the Niagara network, using Niagara’s own Fox protocol.

What the supervisor is for

A typical split of responsibilities:

JACE Supervisor
Talks to field devices (BACnet, Modbus and others) Talks to the JACEs
Runs local logic and schedules Holds master schedules and calendars
Keeps short-term histories Keeps the long-term history archive
Detects alarms Collects, displays, emails and records alarms centrally
Local graphics if needed The main site-wide graphics and web front end

The JACEs keep running if the supervisor goes down. The supervisor adds the overview, the storage and the convenience.

Adding stations to the Niagara network

Under the supervisor’s Drivers › NiagaraNetwork, discover the JACEs and add them as stations. Each connection needs:

  • the JACE’s address, using Foxs (encrypted Fox, port 4911 by default). The old unencrypted Fox port, 1911, shouldn’t be used on new work
  • credentials for a dedicated station-to-station user on the JACE, with only the permissions that connection needs
  • certificate approval: the supervisor must trust the JACE’s certificate (and vice versa), either through properly signed certificates or by approving the host in certificate management

Usually the JACE also adds the supervisor to its own Niagara network, so alarms and histories can flow upwards.

If a connection won’t come up, check the obvious things first: routing between the networks, firewalls blocking 4911, credentials, and certificate approval. Niagara 4.15 added Fox over WebSocket, which lets these connections use port 443 where IT won’t open 4911.

Getting data onto the supervisor

Proxy points. As with any other driver, you can discover a JACE’s points and add them as Niagara proxy points on the supervisor. Use them where the supervisor needs the value permanently, for supervisor-level logic or for alarms raised on the supervisor.

Virtual components. Instead of creating proxy points, the supervisor can browse the JACE’s components “virtually”. They’re only live while someone’s viewing them. That’s ideal for graphics on large sites: you avoid building and maintaining thousands of proxy points just to draw pages.

Histories

Set up history archiving so the JACEs’ histories end up on the supervisor:

  • import descriptors on the supervisor pull histories from a JACE on a schedule, or
  • export descriptors on the JACE push them up

Make sure the archive runs more often than the JACE histories roll over, then check on the supervisor that the data is arriving and is complete. See trending in Niagara 4.

Alarms

On each JACE, add a station recipient that points at the supervisor and link it to the alarm classes that should go up. The supervisor then handles them centrally: console, email, history and acknowledgement. Acknowledging on the supervisor can be passed back to the source station.

Test a real alarm from each JACE through to the supervisor’s console and email before handover. See Niagara 4 alarms.

Master schedules

Create the site’s master schedules and holiday calendars on the supervisor, and share them to the JACEs. Each JACE keeps a synchronised local copy, so plant keeps running to time even if the network to the supervisor fails. See schedules in Niagara 4.

Graphics and navigation

Build the main graphics on the supervisor using virtual components or proxy points, with a site-wide banner and a home page that leads into each building or JACE. Hierarchies work across the whole system, which makes them especially useful here. Graphics built once and reused across identical JACEs save a lot of time; see reusable graphics.

Licensing

Supervisors are licensed according to how much they connect to, typically by the number of JACEs or devices and points. Check the licence covers the full site, with room for growth, before you start adding stations.

A supervisor checklist

  • All JACEs connected over Foxs with dedicated credentials and trusted certificates
  • Histories archiving, with the interval shorter than the JACE roll-over
  • Alarms from every JACE reaching the supervisor console and email
  • Master schedules and calendars syncing to each JACE
  • Graphics working through virtuals or proxies, with consistent navigation
  • Supervisor backed up regularly, with a backup kept off the server
  • Remote access through a secure, IT-approved route (see BMS cyber security basics)

Sources